Last updated
Four outage plans, calculated
All for 24 hours with a 20% battery reserve. “Essentials” is a refrigerator, Wi-Fi router, five LED bulbs and four phone chargers. Fuel is gasoline per day at a light generator load.
| Plan | Running | Biggest surge | Energy per day | Battery | Generator | Gasoline |
|---|---|---|---|---|---|---|
| Essentials only | 255 W | 705 W | 1,930 Wh | 2,838 Wh | 1,000 W | 0.69 gal |
| Winter: plus gas furnace blower | 855 W | 2,055 W | 7,930 Wh | 11,662 Wh | 2,000 W | 2.83 gal |
| Well and sump pump home | 1,955 W | 3,955 W | 4,130 Wh | 6,074 Wh | 3,500 W | 1.47 gal |
| Summer heat: plus window AC | 855 W | 2,055 W | 6,730 Wh | 9,897 Wh | 2,000 W | 2.40 gal |
- The winter plan needs far more energy than the pumps do, because a furnace blower runs for hours while a pump runs for minutes.
- The pump plan uses little energy but needs the biggest generator, because pump start-up surges set the size.
How the plan is calculated
- Energy per day (Wh) = watts × hours per day for every ticked appliance. Energy for the outage = daily energy × outage hours ÷ 24.
- Battery (Wh) = outage energy ÷ 0.85 for inverter losses ÷ (1 − reserve).
- Inverter (W) = the larger of running load × 1.25 and the biggest surge moment ÷ the surge rating, rounded up to a standard size. The surge moment is the running load plus the extra start-up power of the biggest motor.
- Generator running watts = the larger of running load × 1.2 and the surge moment ÷ 1.25, because portable generators typically deliver about 25% more for starting than for running.
- Fuel = energy in kWh ÷ (energy per gallon × generator efficiency). A gallon holds about 35 kWh for gasoline, 40 for diesel and 26.7 for propane. Efficiency is 8%, 12% or 16% by how hard the generator works, since small loads waste a lot.
- Solar to recharge = daily energy ÷ 0.85 ÷ (peak sun hours × 0.75).
It plans for essentials, not a whole house. Real fuel use varies widely by generator and load, so check your model’s fuel chart.
Battery backup or generator?
- Battery backup is quiet, safe indoors and starts instantly, but its capacity is limited and recharging takes sun or grid power. It suits short outages and small essential loads.
- A generator keeps going as long as you have fuel and handles big loads such as pumps. It is loud, needs fuel storage, and must run outdoors.
- A battery plus solar can run a small essential load indefinitely. The “solar to recharge” result shows the panel size for that.
Using it anywhere in the world
- Fuel is shown in gallons and liters, and energy in watt-hours.
- Watts are the same on 120 V and 230 V systems, but check your appliance labels, because heaters and pumps may be rated higher on 230 V.
- Choose generator and inverter output voltage and frequency to match your appliances.
Common planning mistakes
- Sizing for running watts only. Pumps and compressors need a surge several times their running power.
- Forgetting the heating or cooling. A furnace blower or window air conditioner can use more energy than everything else combined.
- Assuming a battery stays full. Keep a reserve and plan to recharge.
- Underestimating fuel. Store enough for the longest outage you want to cover, and store it safely.
- Connecting a generator unsafely. Use a properly installed transfer switch or interlock, fitted by a licensed electrician.
Common questions
How big a battery do I need to keep a refrigerator running in an outage?
A modern refrigerator averages about 150 W while its compressor runs, around 8 hours of every 24, which is about 1.2 kWh a day. With inverter losses and a 20% reserve that takes about 1.8 kWh of battery for each day. Its start-up surge is roughly 600 W, so choose an inverter of at least 500 W.
What size generator do I need for essentials?
For a refrigerator, router, lights and phone chargers, about 1,000 W of running watts is enough. Adding a gas furnace blower raises that to about 2,000 W, and adding a well pump and a sump pump raises it to about 3,500 W, because pump start-up surges set the size.
How much fuel does a generator use per day?
For the essentials plan, the calculator estimates about 0.69 gallons of gasoline a day at light load, and about 2.83 gallons a day with a furnace blower. Real consumption varies widely by generator model and load, so use your model’s fuel chart for a better number.
Should I buy a battery backup or a generator?
For short outages and small loads, battery backup is quieter, safe indoors, and needs no fuel. For multi-day outages or big loads such as pumps and heating, a generator is usually more practical. A battery with solar panels can also run a small essential load for many days, and the calculator shows the panel size you would need.
Can I run my gas furnace in a power outage?
A gas furnace still needs electricity for its blower and ignition, typically 300–800 W with a start-up surge. A battery or generator can run it only if it is connected correctly, usually through a transfer switch or dedicated inlet installed by a licensed electrician. Never run a portable generator inside the house or garage.
Can I power my whole house in an outage?
Only with a much larger system. Central air conditioning, electric ranges and electric water heaters each use thousands of watts. Whole-house backup needs a load calculation and a transfer switch installed by a licensed electrician. Planning for essentials is far cheaper and usually enough for a few days.