Size Your Power / 12V wire gauge chart

12 V and 24 V wire gauge chart

Find the longest cable run for your load at a 3% voltage drop, in AWG and mm², with a fuse size chart and the current ratings behind it.

Last updated

These charts show the longest one-way run of copper cable, from the battery or source to the load, that keeps the voltage drop at 3% or less. A dash means the cable cannot safely carry a fuse sized at 125% of that load, using conservative standard-insulation (60 °C) current ratings. For your own numbers, use the wire gauge and fuse calculator.

12 V chart, AWG sizes

Load14121086421/02/04/0
5 A14 ft · 4.3 m22 ft · 6.8 m36 ft · 10.8 m56 ft · 17.2 m90 ft · 27.4 m143 ft · 43.6 m227 ft · 69.1 m361 ft · 110.1 m455 ft · 138.7 m722 ft · 220.1 m
10 A7 ft · 2.1 m11 ft · 3.4 m18 ft · 5.4 m28 ft · 8.6 m45 ft · 13.7 m72 ft · 21.8 m113 ft · 34.6 m181 ft · 55.0 m227 ft · 69.3 m361 ft · 110.1 m
15 A–7 ft · 2.3 m12 ft · 3.6 m19 ft · 5.7 m30 ft · 9.1 m48 ft · 14.5 m76 ft · 23.0 m120 ft · 36.7 m152 ft · 46.2 m241 ft · 73.4 m
20 A––9 ft · 2.7 m14 ft · 4.3 m22 ft · 6.8 m36 ft · 10.9 m57 ft · 17.3 m90 ft · 27.5 m114 ft · 34.7 m181 ft · 55.0 m
30 A–––9 ft · 2.9 m15 ft · 4.6 m24 ft · 7.3 m38 ft · 11.5 m60 ft · 18.3 m76 ft · 23.1 m120 ft · 36.7 m
40 A––––11 ft · 3.4 m18 ft · 5.5 m28 ft · 8.6 m45 ft · 13.8 m57 ft · 17.3 m90 ft · 27.5 m
50 A–––––14 ft · 4.4 m23 ft · 6.9 m36 ft · 11.0 m45 ft · 13.9 m72 ft · 22.0 m
75 A–––––––24 ft · 7.3 m30 ft · 9.2 m48 ft · 14.7 m
100 A–––––––18 ft · 5.5 m23 ft · 6.9 m36 ft · 11.0 m
150 A––––––––––
200 A––––––––––

12 V chart, metric sizes (mm²)

Load1.52.54610162535507095
5 A10 ft · 3.1 m17 ft · 5.1 m27 ft · 8.2 m40 ft · 12.3 m67 ft · 20.6 m108 ft · 32.9 m169 ft · 51.4 m236 ft · 72.0 m337 ft · 102.9 m472 ft · 144.0 m641 ft · 195.4 m
10 A–8 ft · 2.6 m13 ft · 4.1 m20 ft · 6.2 m34 ft · 10.3 m54 ft · 16.5 m84 ft · 25.7 m118 ft · 36.0 m169 ft · 51.4 m236 ft · 72.0 m321 ft · 97.7 m
15 A––9 ft · 2.7 m13 ft · 4.1 m22 ft · 6.9 m36 ft · 11.0 m56 ft · 17.1 m79 ft · 24.0 m112 ft · 34.3 m157 ft · 48.0 m214 ft · 65.1 m
20 A–––10 ft · 3.1 m17 ft · 5.1 m27 ft · 8.2 m42 ft · 12.9 m59 ft · 18.0 m84 ft · 25.7 m118 ft · 36.0 m160 ft · 48.9 m
30 A––––11 ft · 3.4 m18 ft · 5.5 m28 ft · 8.6 m39 ft · 12.0 m56 ft · 17.1 m79 ft · 24.0 m107 ft · 32.6 m
40 A–––––13 ft · 4.1 m21 ft · 6.4 m30 ft · 9.0 m42 ft · 12.9 m59 ft · 18.0 m80 ft · 24.4 m
50 A––––––17 ft · 5.1 m24 ft · 7.2 m34 ft · 10.3 m47 ft · 14.4 m64 ft · 19.5 m
75 A––––––––22 ft · 6.9 m31 ft · 9.6 m43 ft · 13.0 m
100 A–––––––––24 ft · 7.2 m32 ft · 9.8 m
150 A–––––––––––
200 A–––––––––––

24 V chart, AWG sizes

At 24 V the same cable carries the same current with twice the voltage to spare, so the allowed length doubles for the same load in amps. In practice the same power draws half the amps at 24 V, so the run can be longer still.

Load14121086421/02/04/0
5 A28 ft · 8.6 m45 ft · 13.6 m71 ft · 21.6 m113 ft · 34.4 m180 ft · 54.7 m286 ft · 87.2 m454 ft · 138.2 m722 ft · 220.1 m910 ft · 277.3 m1444 ft · 440.2 m
10 A14 ft · 4.3 m22 ft · 6.8 m36 ft · 10.8 m56 ft · 17.2 m90 ft · 27.4 m143 ft · 43.6 m227 ft · 69.1 m361 ft · 110.1 m455 ft · 138.7 m722 ft · 220.1 m
15 A–15 ft · 4.5 m24 ft · 7.2 m38 ft · 11.5 m60 ft · 18.2 m95 ft · 29.1 m151 ft · 46.1 m241 ft · 73.4 m303 ft · 92.4 m481 ft · 146.7 m
20 A––18 ft · 5.4 m28 ft · 8.6 m45 ft · 13.7 m72 ft · 21.8 m113 ft · 34.6 m181 ft · 55.0 m227 ft · 69.3 m361 ft · 110.1 m
30 A–––19 ft · 5.7 m30 ft · 9.1 m48 ft · 14.5 m76 ft · 23.0 m120 ft · 36.7 m152 ft · 46.2 m241 ft · 73.4 m
40 A––––22 ft · 6.8 m36 ft · 10.9 m57 ft · 17.3 m90 ft · 27.5 m114 ft · 34.7 m181 ft · 55.0 m
50 A–––––29 ft · 8.7 m45 ft · 13.8 m72 ft · 22.0 m91 ft · 27.7 m144 ft · 44.0 m
75 A–––––––48 ft · 14.7 m61 ft · 18.5 m96 ft · 29.3 m
100 A–––––––36 ft · 11.0 m45 ft · 13.9 m72 ft · 22.0 m
150 A––––––––––
200 A––––––––––

Fuse size chart

A common rule is to fuse at about 125% of the continuous load current, rounded up to the next standard rating, and never above the cable’s current rating.

Load2 A5 A10 A15 A20 A30 A40 A50 A80 A100 A150 A200 A
Fuse3 A7.5 A15 A20 A25 A40 A50 A70 A100 A125 A200 A250 A

Cable sizes and current ratings

AWGCopper areaRating, standard insulation (60 °C)Rating, high temperature (90 °C)
180.823 mm²7 A7 A
161.31 mm²10 A10 A
142.08 mm²15 A15 A
123.31 mm²20 A20 A
105.26 mm²30 A30 A
88.37 mm²40 A55 A
613.3 mm²55 A75 A
421.2 mm²70 A95 A
233.6 mm²95 A130 A
142.4 mm²110 A145 A
1/053.5 mm²125 A170 A
2/067.4 mm²145 A195 A
3/085 mm²165 A225 A
4/0107 mm²195 A260 A

The ratings come from copper values in the US National Electrical Code table for conductors, with the small-size limits for 18 to 10 AWG applied. Metric sizes are matched to the next smaller AWG row, which is conservative. Bundled or hot cable should be derated. Marine, vehicle and building codes differ, so check the rules where you live.

How the length is calculated

Maximum one-way length = allowed voltage drop × cable area ÷ (2 × 0.0175 × current). The 0.0175 is the resistivity of copper in ohm-mm² per meter, and the 2 is for the return path. Allowed voltage drop is 3% of the system voltage.

Common questions

What gauge wire do I need for 12 V and 30 amps?

It depends on the distance. For a 30 A load, a fuse of 40 A and 3% voltage drop, 8 AWG covers about 9 ft one way and 6 AWG about 15 ft. The calculator finds the size for your exact length.

How far can I run 12 V wire at 20 amps?

With 10 AWG cable, a 20 A load stays within a 3% voltage drop for about 9 ft (2.7 m) one way. 8 AWG about doubles that. Longer runs need a thicker cable or a higher system voltage.

What is the difference between AWG and mm²?

AWG is the American wire gauge, where a smaller number means a thicker wire, and mm² is the copper cross-section area used in most other countries. They do not match exactly, so choose the nearest size that is large enough in the system your shop uses.

Why does the allowed length shrink as the current goes up?

A cable wastes voltage in proportion to the current through it. Doubling the current doubles the voltage drop on the same cable, so the same drop allows only half the length.

Do I always need a fuse?

Yes, on the positive cable close to the battery. The fuse protects the cable. Choose a rating at about 125% of the load and below the cable’s current rating, and use a fuse rated for DC at your system voltage.

Is 3% voltage drop the right target?

A common guideline for sensitive circuits such as electronics and lighting is 3%, and up to 10% for less critical loads. The wire gauge and fuse calculator lets you choose 2%, 3%, 5% or 10%.

Related

Calculate your exact cable and fuse with the wire gauge and fuse calculator. Charging from the alternator? See the alternator charge time calculator. For the terms used here, see the off-grid power glossary.